Ezi-IO Plus-E DA

Ezi-IO-EN-AD08-T

Settings and Operation

Switch

1. Ethernet IP Setting Switch (SW1, SW2)
These switches set the 4th octet of Ethernet IP. The 1st octet,the 2nd octet, and the 3rd octet are set by GUI. If the switches are set to 255(FF), DHCP function is activated, and IP is automatically set, ignoring the set value.
(Please refer to the manual for details.)

e.g.,) In case of SW2 : 5 and SW1 : 7
        (5×16) + (7×1) = 87
        IP is to be set as 192.168.0.87
2. Output Range Setting Switch (SW3)
SW3 is a switch for setting the output range. You can set the range with the combination of the switches.
• Selecting Input Setting Method
You can select the output setting method with the LSET (SW3.1) switch as follows.
Switch
Mode
LSET
SW3.1
Description
DIP Switch ON Setting output range with DIP switches (SW3.3~SW3.10)
Ethernet communication OFF Setting output range with Ethernet communication
* Set SW3.1 before supplying power to the module.
* SW3.2 is not used.
• Output Range Setting
When using the DIP Switch for setting (SW3.1 = ON), the output range is set as shown in the table below.
Switch
Output Range
CH1 CH2 CH3 CH4
SW3.3 SW3.4 SW3.5 SW3.6 SW3.7 SW3.8 SW3.9 SW3.10
0~5V OFF OFF OFF OFF OFF OFF OFF OFF
-10~10V OFF ON OFF ON OFF ON OFF ON
0~20mA ON OFF ON OFF ON OFF ON OFF
4~20mA ON ON ON ON ON ON ON ON
* Output range of 1~5V and 0~10V can only be set by Ethernet communication.

LED Indications

1. Power Status LED
Name Color Status Description
PWR Red OFF Power is OFF
ON Power is ON
2. Operation Status LED
Name Color Status Description
RUN Green OFF Abnormal Operation
Blinking Normal Operation
3. Ethernet Status LED
Name Color Status Description
LINK1, LINK2 Green OFF Link not Established
ON Link Established
4. Ethernet Status LED
LED Color Status Description
ACT1, ACT2 Yellow OFF Stand-by
Flickering In Operation

Connector

1. Power Connector (CN1)
No. Fuction I/O
1 DC24V Input
2 GND Input
2. Output Signal Connector (CN2)
No. Name Fuction I/O
1 G Analog GND Output
2 V1 Voltage Out 1 Output
3 I1 Current Out 1 Output
4 G Analog GND Output
5 V2 Voltage Out 2 Output
6 I2 Current Out 2 Output
7 G Analog GND Output
8 V3 Voltage Out 3 Output
9 I3 Current Out 3 Output
10 G Analog GND Output
11 V4 Voltage Out 4 Output
12 I4 Current Out 4 Output
3. Ethernet Communication Connector (CN3, CN4)
NO. Function
1 TD+
2 TD-
3 RD+
4 ----
5 ----
NO. Function
6 RD-
7 ----
8 ----
Connector
hood
F.GND

Accessories - Connectors

Purpose Item Part Number Manufacturer
Power (CN1) Terminal Block MC421-38102 DECA
※ The connectors above are supplied with the product. If you are using other parts, please make sure they meet the specifications.

Options - Ethernet Cable

Purpose Part Number Length [m] Remarks
Ethernet Connection
(CN3, CN4)
CGNR-EC-001F
CGNR-EC-002F
CGNR-EC-003F
CGNR-EC-005F
1
2
3
5
· STP(Shielded Twisted Pair) Cable
· Category 5e or higher
· Maximum Length: 100m
· Normal Cable
※ If you need cables with length(in units of 1m) not listed on the table or robot cables, please contact FASTECH for more information.